The IS type is the legacy ELIN design and supports up to 35 positions. It is rated up to 300 kV and 2100 A, which makes it suitable for 765 kV transformers, and it also serves furnace applications where the number of operations is large. The IM type is an alternative to the S type, with ratings up to 300 kV and 1800 A. The IV type is a selector switch design for distribution, sub-transmission and transmission applications, and it offers up to 27 positions at 123 kV and 500 A. The ID type serves special legacy transformer designs in transmission systems, providing up to 23 positions at 123 kV and 400 A.